LZCK350-10 100/5A epoxy resin cast split core current transformer

Epoxy Resin Split Core Current Transformer

The model LZCK350-10 ct is a ring type resin casting split core current transformer. Some clients also called it as TTCC. This model can be used both for measurement and microcomputer protection of electrical equipment in 11KV and 35KV AC power system of compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe Plus... and cable distribution boxes.
We used imported silicon material and using our mature advanced producing technology we make sure our transformer has very goog linear and more than 20 years using life in order to be qualified with all the jobs. The semicircular ring core and secondary windings are vacuum poured by insulated resin.
All of our current transformers are strictly comply IEC60044-1, IEC 61869-2, NTC 2205, GB1208-2006, GB20840.2-2013, ANSI/IEEE C57.13.

 

Wiring diagrams

Front View of Resin Split Core Current Transformer,doule ratio

P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).

Features

  • Size: φ50xφ110x105
  • Support dual ratio;
  • Large burden design;
  • High precision 0.5%;
  • Holding wire diameter: φ45mm;
  • Measurement range 0-1000A AC;
  • Using life more than 20 years;
  • Easily installation, with mounting bracket;
  • High magnetic conductivity silicon steel material;
  • Secondary windings are vacuum poured by insulated resin;
  • 50/5A, 100/5A, 200/5A, 300/5A, 400/5A, 500/5A, 600/5A, 1000/5A;
  • IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006; GB20840.2-2013;

APPLIATIONS

  • Power meter;
  • Meter tester;
  • Energy meter;
  • MV switchgears;
  • Air switch cabinet;
  • Distribution boxes;
  • Power quality meter;
  • Measuring instrument;
  • Ring network cabinet;
  • Current load monitoring;
  • Low voltage metering system;
  • Distribution power transformer monitor system;
 

Parameters

Technical parameters
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI/IEEE C57.13; GB1206-2006;
Rated primary current 30-1000A
Rated load ≤25VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Insulation class E
Material Polyurethane+silicon steel sheets+enameled wire+ABS
Mechanical parameters
Dimensions (W×D×H)(mm) φ50xφ110x105
Jaw cable diameter(mm) 45
Weight (kg) 3.1
Operating conditions
Operating temperature -40°C to +70°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

Technical data

Type LZCK350-10 LZCK350-10 LZCK350-10
Purpose Measuring current transformer Protection current transformer Double winding current transformer
Ratio Accuracy class and rated burden (VA) Accuracy class and rated load (VA) Composite accuracy class and rated load (VA)
I1/I2 0.5 1 3 10P15 10P10 10P5 0.5 1 10P10 10P5
30/1 0.5 1.5 0.75 1.25
50/1 1 2 1.25 2
75/1 2 2.5 3.75 1.25 2 3 2 1 2
100/1 2.5 3.75 5 2 2.5 5 2 2.5 1.5 2.5
200/1 5 2.5 5 3 5 7.5 2.5 2
300/1 10 3.75 5 3 5 7.5 3.75 2.5
400/1 10 5 10 3 5 10 5 2.5
500/1 15 5 10 3.75 6.25 10 5 2.5
600/1 20 7.5 10 5 7.5 10 7.5 5
750/1 25 7.5 10
800/1 25 10 15
1000/1 25 10 15
50/5 2.5 2
75/5 2.5 3
100/5 2.5 5 10 5 2.5 2.5
200/5 7.5 10 20 2.5 5 2.5
300/5 10 15 20 5 2 2.5
400/5 15 15 30 7.5 2.5 5
500/5 25 30 40 7.5 2.5 5
600/5 25 30 50 10 3 7.5
750/5 30 30 50
800/5 30 30 50
1000/5 30 30 50

Selection guide

Model Primary rated current Rated load Aperture (mm) Description (mm) Weight (kg)
LZCK310-10 300-1000A ≤10VA φ50 φ50×φ110×32 1
LZCK322-10 30-1000A ≤10VA φ50 φ50×φ110×52 1.6
LZCK350-10 30-1000A ≤25VA φ50 φ50×φ110×105 3.1
LZCK720-10 30-1000A ≤25VA φ80 φ80×φ110×50 2.1
LZCK2500-10 30-3000A ≤30VA φ120, 140, 160 φ120×φ185×100 7
LZCG530-10 30-1000A ≤20VA φ45 φ45 x φ120 x 65 2.1
LZCG930-10 30-1500A ≤25VA φ60 φ60×φ155×60 3.6
LZCT722-10 30-1500A ≤10VA φ82 φ82×φ130×55 2.3
LZCG2500-10 30-3000A ≤30VA φ120, 140, 160 φ120×φ185×100 7

Ordering information

Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.

Download Catalogue

Related Products