LZCK-55 clamp outdoor waterproof split core current transformer

outdoor IP65 Split core current transformer

The model LZCK-55 split core ct is a 55mm core diameter outdoor split core current transformer. Some clients also called it as outdoor TTCC. Due to its accuracy can be 0.5s and its IP67 protection degree level, this current transformer is widely used together with energy meters for measurement in power utilities. Also this current transformer can be used in outdoor distribution power transformer monitor system.
The semicircular ring core and secondary windings are vacuum poured by insulated resin. Besides infront using field, this model can be used both for measurement and microcomputer protection of electrical equipment in 11KV and 35KV AC power system.
All of our split core current transformers are strictly comply IEC60044-1, IEC 61869-2, NTC 2205, GB1208-2006, GB/T20840.2, ANSI/IEEE C57.13.

 

Features

  • Support dual ratio;
  • IP67 level outdoor;
  • High precision 0.5s;
  • Support install seals;
  • Long-life technology design;
  • Measurement range 0-1000A AC;
  • Holding wire diameter: φ55mm;
  • Easily installation with electricity;
  • Clamp type structure current transformer;
  • Secondary windings are vacuum poured by insulated resin;
  • IEC60044-1, IEC 61869-2, NTC 2205, GB/T20840, ANSI/IEEE C57.13;
  • 100/5A, 200/5A, 300/5A, 400/5A, 500/5A, 600/5A, 750/5A, 800/5A, 1000/5A;

APPLIATIONS

  • Power meter;
  • Meter tester;
  • Energy meter;
  • MV switchgears;
  • Load monitoring;
  • Distribution boxes;
  • Power quality analyzer;
  • Low voltage metering system;
  • Reactive compensation device;
  • Energy consumption monitoring system;
  • Distribution power transformer monitor system;
 

Parameters

Technical parameters
Standards IEC60044-1; IEC 61869-2; NTC 2205; GB1208-2006; GB/T20840.2; ANSI/IEEE C57.13
Accuracy Class 0.5S, 0.5%, 1%, 3%
Range of primary rated current 100-1000A
Range of rated load ≤10VA
Rated frequency 50/60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 150%I1n
Secondary winding power frequency withstand voltage 3kV, 1min
Safety factor rating (FS)<10
Output signal 1A, 5A, 333mV, 1V or 5V (customized)
Safety CAT IV 600V IEC/EN 61010-1
Insulation class E
Flame retardant ABS and UV plastic shell inside, jaw waterproof apron.
Mechanical parameters
Aperture (mm) Φ55
Dimensions (W×D×H)(mm) 180×138×52
Weight (kg) 2
Length of cable 2.5M (standard), 5M, 10M or customized
Cable information 2*16AWG, voltage: 400/720V, outdoor+UV
Color Orange, black or customized
Working conditions
Operating temperature -40°C to +70°C
Storage temperature -40°C to +70°C
Ingress protection IP67
Environment Outdoors or indoors
The height of above sea level 0-3000m
Conditions No existence of severely begrimed, erosive and radioactive gas in the air. Continuous working under the rated current is allowed.
GFUVE company provide outdoor split core ct scheme design customized services!

TECHNICAL DATA

Type LZCK-55 (2.5m cable)
Purpose Measuring current transformer
Ratio Accuracy class and rated load (VA)
I1/I2 0.5S 0.5 1 3
100/1 0.1 1 2.5
150/1 0.1 1 2.5
200/1 1 2.5 2.5 2.5
250/1 1 2.5 2.5 2.5
300/1 1 2.5 2.5 2.5
400/1 2.5 2.5 2.5 2.5
500/1 2.5 2.5 5 5
600/1 2.5 2.5 5 5
800/1 2.5 2.5 5 5
1000/1 2.5 2.5 5 5
100/5 2.5 2.5
150/5 2.5 2.5
200/5 2.5 2.5 5 5
250/5 2.5 2.5 5 5
300/5 5 5 5 5
400/5 5 10 10 10
500/5 5 10 10 10
600/5 5 10 10 10
800/5 5 10 10 10
1000/5 5 10 10 10

Selection Guide

Model Primary rated current Rated load Aperture (mm) Description (mm) Weight (kg)
LZCK-36 100-600A ≤10VA Φ36 128×120×85.5 1.25
LZCK-55 100-1000A ≤10VA Φ55 180×138×52 2
LZCK-80 100-2000A ≤20VA Φ80 185×164×60 2.5
LZCK-120 100-3000A ≤20VA Φ120 225×204×64 2.8
LMCK185-10 300-5000A ≤25VA Φ185 350×283×55 4.5