LZCG930-10 Cheap low voltage Cast Resin Ring Core Current Transformer

low voltage Ring Core Current Transformer

The Model LZCG930-10 CT is a ring type resin casting current transformer. Some clients also called it as TTCC. This current transformer can be used both for measurement and microcomputer protection of electrical equipment in 11KV and 35KV AC power system, It is widely used in not only compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe Plus, Unstitch, Schneider RM6, SM6, Siemens 8DJ10/8DH10, Simosec, FBX, Fluokit, Omar Garbo GA, GAE; SEL TPS(Q); VEI Unifluorc; Eaton SVS/12 ring network, but also cable distribution boxes because of its small size, light weight, operable and convenient installation. It is very convenient that the transformer can be directly installed at the inlet and outlet cables.

 

New magnetic material is taken to be the core of the current transformer, which has high magnetic permeability, low saturation magnetization and good stability. Therefore, the measuring accuracy is higher and the instrument security factor is lower. Since the high quality silicon processed by advanced technology is taken to be the core of the protection windings, which assured the accuracy limit factor is higher.
We used imported silicon material and using our mature advanced producing technology we make sure our transformer has very goog linear and more than 20 years using life in order to be qualified with all the jobs. The ring core and secondary windings are vacuum poured by high quality polyurethane insulated resin ,which has the characteristic of moisture proof, stable performance and dispensing with maintenance.
All of our ring core current transformers are strictly comply IEC60044-1, IEC 61869-2, NTC 2205, GB1208-2006, GB20840.2-2013, ANSI/IEEE C57.13.

Outline drawing

Split core cast resin current transformer

Wiring diagrams

Split core cast resin current transformer

P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).

Features

  • Size:φ60xφ155x60;
  • Support Dual Ratio;
  • Polyurethane resin casting;
  • Measurement range 0-1000A AC;
  • Holding wire diameter: φ60mm;
  • Using life more than 20 years;
  • High precision 0.2s,0.2%, 0.5s,0.5%;
  • Easily installation, with mounting bracket;
  • Protection class 5P20, 5P10, 10P15, 10P10, 10P5;
  • The protection level CT can accept customized design;
  • Secondary windings are vacuum poured by insulated resin;
  • High quality polyurethane resin cast current transformer;
  • 100/5A, 200/5A, 300/5A, 400/5A, 500/5A, 600/5A, 750/5A, 800/5A, 1000/5A;
  • IEC60044-1, IEC61869-2, , NTC 2205, GB1208-2006, GB20840.2, ANSI/IEEE C57.13;

APPLIATIONS

  • Power Meter;
  • Meter tester;
  • Energy meter;
  • MV switchgears;
  • Distribution boxes;
  • Air switch cabinet;
  • Power Quality meter;
  • Measuring instrument;
  • Ring network cabinet;
  • Current load monitoring;
  • Low voltage metering system;
  • Distribution Power transformer monitor system;
 

Parameters

Technical parameters 
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI/IEEE C57.13; GB1206-2006;
Accuracy Class 0.2S, 0.2, 0.5S, 0.5 (IEC61869-2 standard)
Rated primary current 30-1000A
Rated load ≤30VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Ratio 100/5A, 150/5A, 200/5A, 300/5A, 400/5A, 500/5A...1000/5A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Insulation Class A
Material Polyurethane +Silicon steel sheets+Enameled wire+ABS
Mechanical parameters 
Dimensions (W×D×H) (mm) φ60×φ155×60
Jaw cable diameter(mm) 60
Weight (kg) 3.6
Operating conditions 
Operating temperature -40°C to +70°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

Selection guide

Type LZCG930-10
Purpose Measuring current transformer
Rated primary current (AMP) Accuracy class and rated load(VA)
0.2S 0.2 0.5S 0.5
50 2.5 2.5 5 5
100 2.5 5 7.5 7.5
150 5 7.5 10 10
200 7.5 10 15 15
300 10 15 15 15
400 15 15 15 15
500 20 20 20 20
600 20 20 20 20
750 20 20 20 20
800 20 20 20 20
1000 20 20 20 20
Purpose Protection current transformer
Rated primary current (AMP) Accuracy class and rated load(VA)
5P20 5P10 10P15 10P10
30 1 1 1 1
40 1 1 1 1
50 2 2 2 2
75 2 2 2 2
100 2.5 2.5 2.5 2.5
150 2.5 2.5 2.5 2.5
200 5 5 5 5
300 5 5 5 5
400 7.5 7.5 7.5 7.5
500 7.5 10 10 10
600 7.5 10 10 15
Purpose Double winding current transformer
Rated primary current (AMP) Composite accuracy class and rated load(VA)
0.2S 0.5 10P15 10P10
100 2.5 2.5 1 1
150 2.5 3.75 2 2.5
200 5 7.5 2.5 3.75
300 7.5 10 2.5 5
400 10 12.5 3.75 5
500 15 15 3.75 5
600 15 20 3.75 7.5

Selection guide

Model Primary rated current Rated load Secondary output Aperture (mm) Description(mm) Weight (kg)
FU-16 5-200A ≤10 Ohm 333mV,1V, 5V,100mA φ16 38 x 55 x 18 0.06
FU-32 100-600A ≤10VA 333mV,1V, 5V, 1A, 5A φ32 110 x 130 x 41 0.7
FU-36 100-600A ≤2.5VA 333mV,1V, 5V, 1A, 5A φ10, φ16, φ24, φ36 26 × 43 × 27
31 × 50 × 30
43 ×73 × 39
60 × 89 × 43
0.1,
0.12,
0.2,
0.35
FU-80 100-1200A ≤5VA 333mV,1V, 5V, 1A, 5A φ30, φ55, φ80 88 x 129 x 28
108 x 155 x 28
138 x 193 x 28
0.4, 0.55, 0.6
FU-100 300-3000A ≤10VA 333mV,1V, 5V, 1A, 5A φ100 170 x 184.5 x 41 1
FU120 200-4000A ≤10VA 333mV,1V, 5V, 1A, 5A 120 x 130, 120 x 30 166 x 110 x 49
166 x 208 x 49
1.2, 1.7
FU160 500-5000A ≤20VA 1A,5A 160 x 80 144 x 227 x 54 2.8

Ordering information

Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make a order. Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.